Service hotline:

15212101212

DST-80

发布日期:2021-03-03 浏览次数:620



DST-80 circular countercurrent glass fiber reinforced plastic cooling tower

Brief description

  The circular countercurrent cooling tower adopts countercurrent gas-heat exchange technology to achieve cooling effect.Cooling tower adopts anti-corrosion design,no wearing parts,very low repair rate,design service life of 30 years.The main body is made of glass fiber reinforced plastic(FRP),and the tower body is free from corrosion.The steel structure is made of national standard material and hot-dip galvanizing is anticorrosive.The packing is made of new modified PVC material,and the structure is inclined folding packing.The water pouring area is diffused.The water is evenly distributed and the cooling effect is enhanced by rotating atomizing water distribution method.

  Our company according to nearly 20 years of manufacturing experience,the structure design of this series of products made partial improvement,so that its operation is more stable and reliable,the main body is durable,assembly is more convenient,the maintenance rate is very low.The company put an end to the"extensive"production management,the implementation of standardized production,product highly mechanized operation.Products are widely used in petroleum,chemical,smelting,rubber,food,air conditioning,injection molding,pharmaceutical,brewing and other industries of circulating water cooling process.


Circular countercurrent glass fiber reinforced plastic cooling tower

Type
Flow
Dimensions(mm)
Fan diameter
Electric power
net weight
Running heavy
Noise
Piping specifications
(m3/h)
Diameter
Height
(mm)
(kw)
DRY
WET
db(A)
Water ingress
Effluent
Full of water
Sewage
Float

Quick fix

DS-100T
78.1
2700
2400
1450
2.2
450
1650
64.5
125
125
25
25
20

DS-125T
97.5
2700
2400
1450
2.2
540
1740
65.5
125
125
25
25
20

DS-150T
117
3000
2550
1450
4
580
1780
66
150
150
25
25
20

DS-175T
136.8
3300
2750
1750
4
760
1860
66
150
150
25
25
20

DS-200T
156.2
3300
2750
1750
4
780
1880
66
150
150
25
25
20
25


Cooling tower structure

Heading
Directions

Steel structure


This series of cooling towers adopts an anti-corrosion design,and a large number of galvanized parts are used in the internal steel structure so that the internal structure has no corrosion parts and the equipment life is greatly extended.It saves the necessary maintenance costs and directly reduces the cost of the enterprise.The steel parts in the tower are motor brackets,packing brackets,center tubes,etc.The anti-corrosion problem is an important part of the quality assurance of the entire tower.To ensure quality,all the factory steel components are hot-dip galvanized for anti-corrosion treatment.


FRP shell
  It adopts a glass fiber reinforced plastic shell,the overall thickness is 5mm,and the flame retardant oxygen index is≥40.Fully automatic spraying equipment is used for one-time production and molding.The product is beautiful and contains a large amount of glue.The shortcomings of uneven thickness and uneven density of hand-made cracks are eliminated.The material is made of 191#anticorrosive resin and fiber cloth and fiber felt produced by Shandong Fiberglass Group.
Waterproof motor
  It adopts waterproof,moisture-proof,corrosion-resistant special Y series outdoor cooling tower motor,which has good sealing performance and is widely used in cooling tower environments under various conditions.The insulation class is F,the protection class reaches IP55,the motor working voltage is 380V,and the rated frequency is 50Hz.
Cooling fan
  The airfoil type axial flow fan designed for the Department of Engineering Mechanics of Tsinghua University,the blade is made of aluminum alloy,and the blade adopts an adjustable hub,which can be angled according to the requirements.Reasonable aerodynamic force,high efficiency,large air volume,low noise,and corrosion resistance.The designed service life is 15 years.
Water distribution system
  The rotating water distributor is used to distribute water,and the water distribution system has anti-clogging performance.The rotor is made of the aluminum alloy at one time,with a temperature resistance of 120℃.The working pressure is between 0.03-0.08mpa(that is,the head of 3-8 meters).This form of uniform water distribution and high heat dissipation efficiency.Sprinkler pipe material PVC
Cloth water turn head
  With the use of a pipe-type water distribution system,the water distribution system has an anti-clogging performance.
Thermal filler

  Packing is an important part of the cooling tower,and its efficiency depends on the degree of full contact between the cooling water and air in the packing.Our company uses multi-corrugated packing,which has a large water redistribution capacity,low resistance,and good thermal performance.The air can quickly take away the heat in the water.The unique filler flow channel enables the water flow to form a large area of flowing water film on the surface of the filler,prolongs the cooling time of the water in the filler,and improves the water cooling effect.The material is a new modified PVC material with a temperature resistance of 65°C.The performance of this product complies with the Ministry of Energy NDGJ88-89"Cooling Tower Plastic Sprinkling Filling Technical Regulations".


Pipe diameter
  Inlet pipe diameter,outlet pipe diameter,automatic water replenishing ball valve,overflow port
Ladder outside the tower
  The cooling tower is equipped with a climbing ladder,which is convenient for daily inspection and maintenance.

Motor related parameters are introduced

Motor insulation class

Insulation temperature class
Rank A
Rank E
Rank B
RankF
Rank H
Allowable temperature(℃)
105
120
130
155
180
Winding temperature rise limit(K)
60
75
80
100
125
Performance reference temperature(℃)
80
95
100
120
145


The motor protection grade reaches IP55

  IP (Ingress Protection) PROTECTION level system is drafted by the IEC (International Electrotechnical Commission). Electrical appliances are classified according to their dust - proof and moisture - proof properties. IP protection grade is composed of two numbers, the first number represents the lamp from the dust, to prevent the invasion of foreign objects, the second number represents the lamp against moisture, waterproof invasion of the airtight degree, the greater the number means that the protection grade is higher. The meaning of the first number: 0: no protection, no special protection 1: the protection of the solid more than 50mm, can prevent the diameter of more than 50mm of solid foreign bodies into the shell. It can prevent a large area of the human body (such as the hand) from accidentally or accidentally touching the charged or moving part of the shell, but can not prevent the conscious approach to these parts 2: protection of solids greater than 12mm, can prevent the diameter of the larger than 12mm of solid foreign bodies into the shell. Can prevent fingers from touching the charged or moving part of the shell ①3: protection of more than 2.5mm of solid, can prevent the diameter of more than 2.5mm of solid foreign bodies into the shell. Can prevent the thickness or diameter of more than 2.5mm tools, metal wire and so on touching the charged or moving part of the shell ①②4: protection of more than 1mm of solid, can prevent the diameter of more than 1mm of solid foreign bodies into the shell. Can prevent the diameter or thickness of more than 1mm wire or strip touching the live or running part of the shell ①②5: dustproof, can prevent dust from entering to affect the normal operation of the product, completely prevent touching the live or moving part of the shell. 6: dust tight, can completely prevent dust from entering the shell, completely prevent hit shell charged or exercise part of the meaning of the second number: 0: no protection, there is no specific protective 1: drip-proof, vertical drop of water should not go into the motor internal 2:15 o drip-proof, with a plumb line into 15 o Angle within the scope of drop water, should not directly into the motor internal 3: water spray, water and the plumb line into 60 o Angle within the scope of the spray water, should not go into the motor internal 4: splash, splash water on any direction motor should be no harmful effects 5: water spray, spray any direction for motor should be no harmful effects 6: Prevent water waves or impose, violent waves or strong water should be no harmful effects on the motor 7: flooding, motor under pressure and time stipulated in the submerged in the water, the water inflow should be no harmful effect on 8: scuba diving, motor in the provisions under the pressure of the long soak in the water, the water inflow should have no harmful effects commonly used in the application of motor protection grade IP11, IP21, IP22, IP23, IP44, IP54 or IP55, etc.